HC
GV2ME20
Delivery time: In stock
Range of Product
TeSys GV2
range
TeSys Deca
TeSys Deca
device short name
GV2ME
product name
TeSys GV2
TeSys Deca
Product or Component Type
Motor circuit breaker
Device Application
Motor protection
trip unit technology
Thermal-magnetic
poles description
3P
network type
AC
utilisation category
AC-3 IEC 60947-4-1
Category A IEC 60947-2
network frequency
50/60 Hz IEC 60947-4-1
fixing mode
35 mm symmetrical DIN rail clipped
Panel screwed with adaptor plate)
operating position
Any position
motor power kW
7.5 kW 400/415 V AC 50/60 Hz
9 kW 500 V AC 50/60 Hz
15 kW 690 V AC 50/60 Hz
breaking capacity
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
8 kA Icu 440 V AC 50/60 Hz IEC 60947-2
6 kA Icu 500 V AC 50/60 Hz IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % 230/240 V AC 50/60 Hz IEC 60947-2
75 % 690 V AC 50/60 Hz IEC 60947-2
75 % 500 V AC 50/60 Hz IEC 60947-2
50 % 400/415 V AC 50/60 Hz IEC 60947-2
50 % 440 V AC 50/60 Hz IEC 60947-2
Control Type
Push-button
Line Rated Current
18 A
thermal protection adjustment range
13…18 A
magnetic tripping current
223 A
[Ue] rated operational voltage
690 V AC 50/60 Hz IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz IEC 60947-2
[Ith] conventional free air thermal current
18 A IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-2
power dissipation per pole
2.5 W
mechanical durability
100000 cycles
electrical durability
100000 cycles AC-3 415 V
415 V
maximum operating rate
25 cyc/h
rated duty
Continuous IEC 60947-4-1
tightening torque
15.05 lbf.in (1.7 N.m) screw clamp terminals
mechanical robustness
Shocks 30 Gn IEC 60068-2-27
Vibrations 5 Gn, 5...150 Hz IEC 60068-2-6
phase failure sensitivity
Yes IEC 60947-4-1
Height
3.50 in (89 mm)
Width
1.77 in (45 mm)
Depth
3.09 in (78.5 mm)
Net Weight
0.57 lb(US) (0.26 kg)
color
Dark grey
suitability for isolation
Yes IEC 60947-1 § 7-1-6