HC
GV3P32
Delivery time: In stock
Range of Product | TeSys GV3 |
---|---|
range |
TeSys Deca TeSys Deca |
device short name | GV3P |
product name |
TeSys GV3 TeSys Deca |
Product or Component Type | Motor circuit breaker |
Device Application | Motor protection |
trip unit technology | Thermal-magnetic |
poles description | 3P |
---|---|
network type | AC |
utilisation category | AC-3 IEC 60947-4-1 |
network frequency | 50/60 Hz IEC 60947-4-1 |
fixing mode |
35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws) |
operating position | Any position |
motor power kW |
15 kW 400/415 V AC 50/60 Hz 18.5 kW 500 V AC 50/60 Hz 22 kW 690 V AC 50/60 Hz |
breaking capacity |
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 12 kA Icu 500 V AC 50/60 Hz IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity |
100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 50 % 500 V AC 50/60 Hz IEC 60947-2 50 % 690 V AC 50/60 Hz IEC 60947-2 |
Control Type | Rotary handle |
Line Rated Current | 32 A |
thermal protection adjustment range | 23…32 A |
magnetic tripping current | 448 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
[Ith] conventional free air thermal current | 32 A IEC 60947-4-1 |
[Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
power dissipation per pole | 8 W |
mechanical durability | 50000 cycles |
electrical durability | 50000 cycles AC-3 415 V In |
maximum operating rate | 25 cyc/h |
rated duty | Continuous IEC 60947-4-1 |
tightening torque |
44.25 lbf.in (5 N.m) EverLink BTR screw connectors 0.04 in² (25 mm²) 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.05 in² (35 mm²) |
mechanical robustness |
Shocks 15 Gn for 11 ms closed IEC 60068-2-27 Shocks 30 Gn for 11 ms opened IEC 60068-2-27 Vibrations 4 Gn, 5...300 Hz IEC 60068-2-6 |
phase failure sensitivity | Yes IEC 60947-4-1 |
Height | 5.20 in (132 mm) |
Width | 2.17 in (55 mm) |
Depth | 5.35 in (136 mm) |
Net Weight | 2.12 lb(US) (0.96 kg) |
color | Dark grey |
suitability for isolation | Yes IEC 60947-1 |