ZLL
GV3P65
delivery time:4-6 weeks
range of product
TeSys GV3
range
TeSys Deca
TeSys Deca
device short name
GV3P
product name
TeSys GV3
TeSys Deca
product or component type
Motor circuit breaker
device application
Motor protection
trip unit technology
Thermal-magnetic
poles description
3P
network type
AC
utilisation category
AC-3 conforming to IEC 60947-4-1
network frequency
50/60 Hz conforming to IEC 60947-4-1
fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws)
operating position
Any position
motor power kW
55 kW at 690 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
30 kW at 400/415 V AC 50/60 Hz
breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
control type
Rotary handle
[In] rated current
65 A
thermal protection adjustment range
48…65 A
magnetic tripping current
910 A
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ith] conventional free air thermal current
65 A conforming to IEC 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-2
power dissipation per pole
8 W
mechanical durability
50000 cycles
electrical durability
50000 cycles for AC-3 at 415 V In
maximum operating rate
25 cyc/h
rated duty
Continuous conforming to IEC 60947-4-1
tightening torque
5 N.m on EverLink BTR screw connectors for cable 25 mm²
8 N.m on EverLink BTR screw connectors for cable 35 mm²
mechanical robustness
Shocks: 15 Gn for 11 ms closed conforming to IEC 60068-2-27
Shocks: 30 Gn for 11 ms opened conforming to IEC 60068-2-27
Vibrations: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
phase failure sensitivity
Yes conforming to IEC 60947-4-1
height
132 mm
width
55 mm
depth
136 mm
net weight
0.96 kg
colour
Dark grey
suitability for isolation
Yes conforming to IEC 60947-1